FCM400 Series - Long Form Datasheet by XP Power

View All Related Products | Download PDF Datasheet
FCM400 Series
Integral Low Noise Fan
400 W Output Power
600 W Peak Rating 500 ms
Screw Terminals
Class B Conducted Emissions
5 V Standby Rail
80 V - 275 VAC Input Operation
IT & Medical Safety Approvals
Remote On/Off & Power Fail Signal as Standard
The FCM400 AC-DC power supply provides upto 400 W continuous and 600 W peak output power for up to 0.5 seconds.
Packaged in a compact 6” (152 mm) x 4” (102 mm) x 1.9” (49 mm) and certified to IEC60950 & IEC60601 family safety approvals, the
FCM400 can be easily integrated into a wide range of both industrial and medical applications. A low noise fan allows quiet operation
at full power from -10 ºC to 50 ºC and 50% power at +70 ºC.
The unit comprises of a main output with voltages from 12-48 VDC and a peripheral output providing a 5 VDC standby supply which
can be utilitsed with the signals and control features of the unit to provide detection of loss of AC input and remote on/off control.
xppower.com
2
Input Characteristics
Characteristic Minimum Typical Maximum Units Notes & Conditions
Input Voltage - Operating 80 115/230 275 VAC Derate output power <90 VAC. See fig 1.
Power fail signal cannot be used <90 VAC.
Input Frequency 47 50/60 63 Hz
Power Factor >0.9 EN61000-3-2 class A compliant
Input Current - No Load 0.11/0.15 A 115/230 VAC
Input Current - Full Load 4.1/2.1 A 115/230 VAC
Inrush Current 60 A 230 VAC, 25 şC
Earth Leakage Current 100/165 260 μA 115 VAC 60 Hz/230 VAC 50 Hz (Typ),
264 VAC/60 Hz (Max.)
Input Protection F10 A/250 V internal fuse in both line and neutral
Output Characteristics
Characteristic Minimum Typical Maximum Units Notes & Conditions
Output Voltage - V1 12 48 VDC See Models and Ratings table
Initial Set Accuracy ±0.5 (V1) , ±5 (V2) % 50% load, 115/230 VAC
Output Voltage Adjustment ±10 % V1 only via potentiometer. See mech. details (page 11).
Minimum Load 0 A
Start Up Delay 1 s 230 VAC full load (see fig.2)
Hold Up Time 20 35 ms 90 VAC full load (see fig.3)
Drift ±0.2 % After 20 min warm up
Line Regulation ±0.5 % 90-264 VAC
Load Regulation ±1 (V1) , ±5 (V2) % 0-100% load.
Transient Response - V1 4 % Recovery within 1% in less than 500 μs
for a 50-75% and 75-50% load step
Over/Undershoot - V1 5 %
Ripple & Noise 0.5 1 (V1), 2 (V2) % pk-pk 20 MHz bandwidth (see fig.4 & 5)
Overvoltage Protection 115 140 % Vnom DC. Output 1 only, recycle input to reset
Overload Protection 150 165 % I nom Output 1 only, auto reset (see fig.6)
Short Circuit Protection Continuous (see fig. 6)
Temperature Coefficient 0.05 %/˚C
Overtemperature Protection °C Auto recovery - temperature of main transformer
Models and Ratings
Output Power Output Voltage V1 Output Current V1 Standby Supply V2 Model Number
P nom P peak (1) I nom I peak (1)
400 W 600 W 12.0 VDC 33.3 A 50 A 5.0 V/0.5 A FCM400PS12
400 W 600 W 15.0 VDC 26.6 A 40 A 5.0 V/0.5 A FCM400PS15
400 W 600 W 24.0 VDC 16.6 A 25 A 5.0 V/0.5 A FCM400PS24
400 W 600 W 28.0 VDC 14.2 A 21.4 A 5.0 V/0.5 A FCM400PS28
400 W 600 W 36.0 VDC 11.1 A 16.7 A 5.0 V/0.5 A FCM400PS36
400 W 600 W 48.0 VDC 8.3 A 12.5 A 5.0 V/0.5 A FCM400PS48
Notes:
1. Peak duration is 500 ms max, average power must not exceed 400 W.
ompm PMW ,,__________ I‘v—‘ 27 Sup m w w an mum. 1295» mm A W 1 mm mmrmms ‘ ‘ ‘ Wxxx mummm ow Aoexznv
xppower.com
3
Start Up Delay From AC Turn On
Figure. 2
V1 & V2 start up example
from AC turn on (1.5 s)
Hold Up Time From Loss of AC
Figure 3
V1 hold up example at 400 W
load with 90 VAC input (42 ms)
AC
V2
AC
V1
Figure. 1
400
360
300
320
540
80 85 275
Input Voltage (VAC)
Peak Power Availability
Output Power (W)
600
90 264
Input Voltage Derating
V1
Ag Ill’lehmlngin 1t! oz: 21 21 San: zmn YUEDEC 2| zzumsznm A, Mm anurIE x v n, VI 0 w wn Manual 1 v H! zsmv 719 5:1an
Output Ripple & Noise
Figure 4
V1 FCM400PS12 (full load)
50 mV pk-pk ripple. 20 MHz BW
Figure 5
V1 FCM400PS24 (full load)
38 mV pk-pk ripple. 20 MHz BW
xppower.com
4
Output Overload Characteristic
Figure 6
Typical V1 Overload
Characteristic
(FCM400PS12 shown)
0
2
4
6
8
10
12
14
0 2 4 6 32 34 36 38 40
Output Current (A)
Output Volts (V)
xppower.com
Xxxxxxxxxx
5
General Specifications
Characteristic Minimum Typical Maximum Units Notes & Conditions
Efficiency 87 % Full load (see fig.7 & 8 )
Isolation: Input to Output
Input to Ground
Output to Ground
4000 VAC
1500 VAC
500 VAC
Switching Frequency 70 / 65 kHz PFC / Main Converter.
Power Density 13.9 W/in3
Mean Time Between Failure 236 kHrs MIL-HDBK-217F, Notice 2
+25 °C GB
Weight 1.8 (800) lb (g)
Efficiency Versus Load
40%
50%
60%
70%
80%
90%
100%
10 20 30 40 50 60 70 80 90 100
Efficiency
Load (%)
230Vac input
40%
50%
60%
70%
80%
90%
100%
10 20 30 40 50 60 70 80 90 100
Efficiency
Load (%)
230VAC input
Figure 7
FCM400PS12
Figure 8
FCM400PS24
I I I I I I I I I I I I I m pImIsIIIwII m; Hsmmfinfi I m PMIMEWIISM mm: zIsIIIIIqu I IIYI IIIIIII I I I PF m II I W I I I I w am me my Mmmxzsmsn om. w w Mznnmzsnksh .nMI
Figure 10
Power Fail signal example
at AC switch off
PF
V1
AC
V2
PF
V1
Figure 11
V1 warning time example at Power Fail signal 230
VAC 400 W load (31 ms)
xppower.com
6
Signals
Power Fail
Figure 9
Pin 7 CON 8
Power Fail
Collector
Power Fail
Emitter
Pin 8 CON 8
POWER SUPPLY
Transistor On (<0.8 V): Input & Output Not OK
Transistor Off (>4.5 V): Input & Output OK
2K2
5 V Standby Rtn
Pin 1, 3 & 5
CON 8
Pin 2, 4 & 6
CON 8
5 V Standby
Signal Connector
8V Max 3 mA
Characteristic Notes & Conditions
Signals
Power Fail Uncomitted opto isolated transistor, normally off when AC is good (see fig.9 - 11)
Provides 5 ms (typically 20-30ms) warning of loss of output from AC failure
Remote On/Off (Inhibit/Enable) Uncommited isolated optocoupler diode, powered diode inhibits the supply (see fig.12-17)
Standby Supply V2 Isolated 5 V/0.5 A supply, always present when AC supplied.
| | | M | N I M I M I I I ' _________ m SInuel mum IAIm NEIMIHNIIH I I I I mun-5 I.IIIIIIIIIIIIII III Im 5w MInmzswsn 311mm: I.“ mum-mm was ummmm I I I I I I , , I’, m IWIIIIIIIIIIIIIIIIIIIIIII Im 5w anmuzgs» mm:
xppower.com
7
Signals
Remote On/Off (Inhibit/Enable)
Inhibit Hi
Pin 10 CON 8
POWER SUPPLY
1K
Signal Connector
Inhibit Lo
Pin 9 CON 8
5 V Standby
2, 4 & 6 CON 8
Logic GND Pin
1, 3 & 5 CON 8
5 mA 8 V Max
Figure 12
Inhibit (Hi)
Figure 13
Inhibit (Lo)
Figure 14
Example of outputs
switching off when
Inhibit (Lo) configuration
used & switch closed
Inhibit
V2
V1
8 V Max
Inhibit Hi
Pin 10
POWER SUPPLY
1K
Signal Connector
Inhibit Lo
Pin 9 CH 1
5 V Standby
Pin 2, 4 & 6
CON 8
Logic GND
Pin 1, 3 & 5
CON 8
5 mA
CON 8
Figure 15
Example of outputs
switching on when
Inhibit (Lo) configuration
used & switch open
Inhibit
V2
V1
l’l Li
Environmental
Characteristic Minimum Typical Maximum Units Notes & Conditions
Operating Temperature -10 +70 şC Derate linearly from +50 şC at 2.5%/şC
to 50% at 70 şC. See fig.18.
Warm up Temperature 20 Minutes
Storage Temperature -40 +85 şC
Cooling Forced cooled via low noise intregal fan
Humidity 5 95 %RH Non-condensing
Operating Altitude 3000 m
Shock
3 x 30 g/11 ms shocks in both +ve & -ve
directions along the 3 orthogonal axis,
total 18 shocks.
Vibration Single axis 10-500 Hz at 2 g x 10 sweeps
xppower.com
Xxxxxxxxxx
8
Inhibit Hi
Pin 10
CON 8
POWER SUPPLY
1K
Pin 1, 3 & 5, CON 8
Inhibit Lo
Pin 9
CON 8
5 V Standby
Pin 2, 4 & 6 CON 8
Logic GND
1K
5 mA
Signal Connector
Figure 16
Enable (Hi)
Figure 17
Enable (Lo)
Remote On/Off (Inhibit/Enable)
XxxxxxxxxxSignals
Notes
1. At AC switch on the output (VI) may momentarily rise when the unit is disabled using the 5 V standby in conjunction with the Remote On/Off function.
xppower.com
9
Electromagnetic Compatibility - Immunity
Phenomenon Standard Test Level Criteria Notes & Conditions
Low Voltage PSU EMC EN61204-3 High severity level as below
Harmonic Current EN61000-3-2 Class A
Radiated EN61000-4-3 3 A
EFT EN61000-4-4 3 A
Surges EN61000-4-5 Installation class 3 A
Conducted EN61000-4-6 3 A
Dips and Interruptions
EN61000-4-11
Dip: 30% 10 ms A
Dip: 60% 100 ms B
Dip: 100% 5000 ms B
EN60601-1-2
(EN61000-4-11)
Dip: 30% 500 ms A
Dip: 60% 100 ms A Requires load derating to approx TBA% with
100 VAC input.
Dip: 100% 10 ms A
Int.: >95% 5000 ms B
Figure 18
Derating Curve
400
300
100
200
500
-10 050
Ambient Temperature (°C)
Peak Power Availability
Output Power (W)
600
10 40
0
60 70
Electromagnetic Compatibility - Emissions
Phenomenon Standard Test Level Criteria Notes & Conditions
Conducted EN55011/22 Class B
Radiated EN55011/22 Class A
Voltage Fluctuations EN61000-3-3
' h
xppower.com
10
Safety Agency Approvals
Equipment Protection Class Safety Standard Notes & Conditions
Class I IEC60950-1:2005 Ed 2 & IEC60601-1 Ed 3 See safety agency conditions of
acceptibility for details
Safety Agency Safety Standard Category
CB Report UL Cert #US/15598/UL, IEC60950-1:2005 Ed 2 Information Technology
UL UL File #E139109-A43-UL, UL60950-1 (2007), CSA 22.2 No.60950-1-07 Ed 2 Information Technology
TUV TUV Certificate # B 10 09 57396 081, EN60950-1/A11 2009 Information Technology
CE LVD
Safety Agency Safety Standard Category
CB Report Certificate #US/17946/UL, IEC60601-1 Ed 3 Including Risk Management Medical
UL UL File # E146893, ANSI/AAMI ES 60601-1:2005 & CSA C22.2 No. 60601-1:08 Medical
TUV EN60601-1:2006 Medical
Means of Protection Category
Primary to Secondary 2 x MOPP (Means of Patient Protection) IEC60601-1 Ed 3
Primary to Earth 1 x MOPP (Means of Patient Protection)
lnpm Cunnecmr CON 2 Tyco pan “3404455
xppower.com
Xxxxxxxxxx
07-Nov-11
Mechanical Details
OUTPUT VOLTAGE
ADJUSTMENT
OUTPUT TERMINALS
M4 SCREWS IN 2
POSITIONS. TORQUE
TO 90 cNm Max.
SIGNALS CONNECTOR CON8
10-WAY JST-BIOB-PDHSS
OUTPUT TERMINALS
ALLOW CONNECTION
FROM EITHER TOP OR SIDE
2
1
6.00 ±0.02
(152.4 ±0.5)
1.93 ±0.02
(49.0 ±0.5)
4.00 ±0.02
(101.6 ±0.5)
0.96
(24.3)
2.10
(53.4)
3.35
(85.0)
INPUT CONNECTOR
Pin 9
NOT INCLUDING OUTPUT
TERMINAL SCREWS
HEIGHT INCLUDES
EMBOSSED FAN COVER
Pin 10
Pin 1Pin 2
M3 MOUNTING HOLES (IN 2 POSITIONS). MAX. PENETRATION
BY SCREW TO BE 3.5mm FROM OUTSIDE FACE OF CHASSIS
3.94
(100.0)
2.95
(75.0)
0.52
(13.3)
1.03
(26.2)
M3 MOUNTING HOLES (IN 4 POSITIONS). MAX. PENETRATION
BY SCREW TO BE 2.5mm FROM BOTTOM FACE OF CHASSIS
1. Dimensions shown in inches (mm).
Tolerance: ±0.02 (±0.5)
2. Weight: 1.8 lb (800g).
Notes
Pin 1 Line
Pin 2 Neutral
Pin 3 Earth
J1 mates with Tyco MTA-156 & 5L-156 product lines
Signals Connector CON 8
15 V Standby Return
25 V Standby
35 V Standby Return
45 V Standby
55 V Standby Return
65 V Standby
7Power Fail (Collector)
8Power Fail (Emitter)
9Remote On / Off (Cathode)
10 Remote On / Off (Anode)
Mating plug: JST p/n PHDR-10VS
Contact: 26-22 AWG JST p/n SPHD-001T-P0.5