TMCM-1021 Firmware Manual Datasheet

4;? QJ coolStep‘“ stallGuard'i A TRINAMIC MOTION CONTROL
MODULE FOR STEPPER MOTORS MODULE
TRINAMIC Motion Control GmbH & Co. KG
Hamburg, Germany
www.trinamic.com
Firmware Version V1.29
TMCL™ FIRMWARE MANUAL
+ + TMCM-1021
+ +
UNIQUE FEATURES:
1-Axis Stepper
Controller / Driver
24V DC
up-to 0.7A RMS / 1.4A RMS
RS485 Interface
sensOstep™ Encoder
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 2
www.trinamic.com
Table of Contents
1 Features ........................................................................................................................................................................... 4
2 Putting the Module into Operation ........................................................................................................................ 6
2.1 Basic Set-Up .......................................................................................................................................................... 6
2.1.1 Connecting the Module ............................................................................................................................... 6
2.1.2 Start the TMCL-IDE Software Development Environment ................................................................. 7
2.2 Using TMCL Direct Mode .................................................................................................................................... 8
2.2.1 Important Motor Settings ........................................................................................................................... 9
2.3 Testing with a Simple TMCL Program ......................................................................................................... 10
3 TMCL and the TMCL-IDE: Introduction ................................................................................................................. 11
3.1 Binary Command Format ................................................................................................................................ 11
3.2 Reply Format ....................................................................................................................................................... 12
3.2.1 Status Codes ................................................................................................................................................. 13
3.3 Standalone Applications .................................................................................................................................. 13
3.4 TMCL Command Overview .............................................................................................................................. 13
3.4.1 TMCL Commands ......................................................................................................................................... 13
3.4.2 Commands Listed According to Subject Area .................................................................................... 14
3.5 Commands ........................................................................................................................................................... 18
3.5.1 ROR (rotate right) ........................................................................................................................................ 18
3.5.2 ROL (rotate left) ........................................................................................................................................... 19
3.5.3 MST (motor stop)......................................................................................................................................... 20
3.5.4 MVP (move to position) ............................................................................................................................ 21
3.5.5 SAP (set axis parameter) ........................................................................................................................... 23
3.5.6 GAP (get axis parameter) .......................................................................................................................... 24
3.5.7 STAP (store axis parameter) ..................................................................................................................... 25
3.5.8 RSAP (restore axis parameter) ................................................................................................................. 26
3.5.9 SGP (set global parameter) ...................................................................................................................... 27
3.5.10 GGP (get global parameter)...................................................................................................................... 28
3.5.11 STGP (store global parameter) ................................................................................................................ 29
3.5.12 RSGP (restore global parameter) ............................................................................................................ 30
3.5.13 RFS (reference search) ................................................................................................................................ 31
3.5.14 SIO (set output) ........................................................................................................................................... 32
3.5.15 GIO (get input/output) ............................................................................................................................... 34
3.5.16 CALC (calculate) ............................................................................................................................................ 36
3.5.17 COMP (compare)........................................................................................................................................... 37
3.5.18 JC (jump conditional) ................................................................................................................................. 38
3.5.19 JA (jump always) ......................................................................................................................................... 39
3.5.20 CSUB (call subroutine) ............................................................................................................................... 40
3.5.21 RSUB (return from subroutine) ................................................................................................................ 41
3.5.22 WAIT (wait for an event to occur) ......................................................................................................... 42
3.5.23 STOP (stop TMCL program execution) ................................................................................................... 43
3.5.24 SCO (set coordinate) ................................................................................................................................... 44
3.5.25 GCO (get coordinate) .................................................................................................................................. 45
3.5.26 CCO (capture coordinate) .......................................................................................................................... 46
3.5.27 ACO .................................................................................................................................................................. 47
3.5.28 CALCX (calculate using the X register) .................................................................................................. 48
3.5.29 AAP (accumulator to axis parameter) .................................................................................................... 49
3.5.30 AGP (accumulator to global parameter) ............................................................................................... 50
3.5.31 CLE (clear error flags) ................................................................................................................................. 51
3.5.32 VECT (set interrupt vector) ........................................................................................................................ 52
3.5.33 EI (enable interrupt) ................................................................................................................................... 53
3.5.34 DI (disable interrupt) .................................................................................................................................. 54
3.5.35 RETI (return from interrupt) ..................................................................................................................... 55
3.5.36 Customer Specific TMCL Command Extension (UF0… UF7/user function) ................................... 56
3.5.37 Request Target Position Reached Event ............................................................................................... 57
3.5.38 TMCL Control Functions ............................................................................................................................. 58
4 Axis Parameters .......................................................................................................................................................... 60
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 3
www.trinamic.com
4.1 Velocity Calculation ........................................................................................................................................... 66
4.2 stallGuard2 ........................................................................................................................................................... 67
4.3 coolStep Related Axis Parameters ................................................................................................................ 67
5 Global parameters ...................................................................................................................................................... 69
5.1 Bank 0 ................................................................................................................................................................... 69
5.2 Bank 1 ................................................................................................................................................................... 71
5.3 Bank 2 ................................................................................................................................................................... 72
5.4 Bank 3 ................................................................................................................................................................... 73
6 Hints and Tips ............................................................................................................................................................. 74
6.1 Reference Search ............................................................................................................................................... 74
6.2 Changing the Prescaler Value of an Encoder ............................................................................................ 77
6.3 Using the RS485 Interface .............................................................................................................................. 77
7 TMCL Programming Techniques and Structure ................................................................................................. 78
7.1 Initialization ........................................................................................................................................................ 78
7.2 Main Loop ............................................................................................................................................................ 78
7.3 Using Symbolic Constants .............................................................................................................................. 78
7.4 Using Variables .................................................................................................................................................. 79
7.5 Using Subroutines ............................................................................................................................................. 79
7.6 Mixing Direct Mode and Standalone Mode ................................................................................................ 80
8 Life Support Policy ..................................................................................................................................................... 81
9 Revision History .......................................................................................................................................................... 82
9.1 Document Revision ........................................................................................................................................... 82
9.2 Firmware Revision ............................................................................................................................................ 82
10 References .................................................................................................................................................................... 83
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 4
www.trinamic.com
1 Features
The TMCM-1021 is a single axis controller/driver module for 2-phase bipolar stepper motors with state of
the art feature set. It is highly integrated, offers a convenient handling and can be used in many
decentralized applications. The module can be mounted on the back of NEMA11 (28mm flange size) and
has been designed for coil currents up to 0.7A RMS (low current range, programmable) or 1.4A RMS (high
current range, programmable, new additional range since hardware version 1.4) and 24V DC supply
voltage. With its high energy efficiency from TRINAMIC’s coolStep™ technology cost for power consumption is
kept down. The TMCL™ firmware supports remote control (direct mode) and standalone operation (with
TMCL program being executed on the TMCM-1021 itself).
MAIN CHARACTERISTICS
Highlights
- Motion profile calculation in real-time
- On the fly alteration of motor parameters (e.g. position, velocity, acceleration)
- High performance microcontroller for overall system control and serial communication protocol
handling
- For position movement applications, where larger motors do not fit and higher torques are not
required
Bipolar stepper motor driver
- Up to 256 microsteps per full step
- High-efficient operation, low power dissipation
- Dynamic current control
- Integrated protection
- stallGuard2 feature for stall detection
- coolStep feature for reduced power consumption and heat dissipation
Encoder
- sensOstep magnetic encoder (max. 1024 increments per rotation) e.g. for step-loss detection under
all operating conditions and positioning supervision
Interfaces
- Up to 4 multi-purpose inputs (2 shared with general purpose outputs)
- 2 general purpose outputs
- RS485 2-wire communication interface
Software
- TMCL: standalone operation or remote controlled operation,
program memory (non volatile) for up to 876 TMCL commands, and
PC-based application development software TMCL-IDE available for free.
Electrical and mechanical data
- Supply voltage: +24V DC nominal (9… 28V DC max.)
- Motor current: up to 0.7A RMS (low current range, programmable) or 1.4A RMS (high current range,
programmable, new additional range since hardware version 1.4)
Refer to separate Hardware Manual, too.
W
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 5
www.trinamic.com
TRINAMICS UNIQUE FEATURES EASY TO USE WITH TMCL
stallGuard2 stallGuard2 is a high-precision sensorless load measurement using the back EMF on the
coils. It can be used for stall detection as well as other uses at loads below those which
stall the motor. The stallGuard2 measurement value changes linearly over a wide range
of load, velocity, and current settings. At maximum motor load, the value goes to zero or
near to zero. This is the most energy-efficient point of operation for the motor.
Load
[Nm]
stallGuard2
Initial stallGuard2
(SG) value: 100%
Max. load
stallGuard2 (SG) value: 0
Maximum load reached.
Motor close to stall.
Motor stalls
Figure 1.1 stallGuard2 load measurement SG as a function of load
coolStep coolStep is a load-adaptive automatic current scaling based on the load measurement via
stallGuard2 adapting the required current to the load. Energy consumption can be
reduced by as much as 75%. coolStep allows substantial energy savings, especially for
motors which see varying loads or operate at a high duty cycle. Because a stepper motor
application needs to work with a torque reserve of 30% to 50%, even a constant-load
application allows significant energy savings because coolStep automatically enables
torque reserve when required. Reducing power consumption keeps the system cooler,
increases motor life, and allows reducing cost.
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0 50 100 150 200 250 300 350
Efficiency
Velocity [RPM]
Efficiency with coolStep
Efficiency with 50% torque reserve
Figure 1.2 Energy efficiency example with coolStep
The things you need: PRECAUTIONS Connect R54! erface and power suggly. Figure 2.1: Starting up
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 6
www.trinamic.com
2 Putting the Module into Operation
Here you can find basic information for putting your TMCM-1021 into operation. If you are already
common with TRINAMICs modules you may skip this chapter.
The things you need:
- TMCM-1021 with fitting motor
- RS485 interface converter with cables
- Nominal supply voltage +24V DC for your module
- TMCL-IDE program and PC
2.1 Basic Set-Up
The following paragraph will guide you through the steps of connecting the unit and making first
movements with the motor.
2.1.1 Connecting the Module
PRECAUTIONS
Do not connect or disconnect the TMCM-1021 while powered!
Do not connect or disconnect the motor while powered!
Do not exceed the maximum power supply voltage of 28V DC!
Note, that the module is not protected against reverse polarity!
START WITH POWER SUPPLY OFF!
Stepper
Motor
Pin 1 B2
Pin 2 B1
Pin 3 A2
Pin 4 A1
Converter
e.g. USB-2-485
1
1
RS485
Pin 1 GND
Pin 3 RS485+
Pin 4 RS485-
Note, that the
GND pin has to be
used for the
power supply and
for the RS485
interface.
Power Supply
Pin 1 GND
Pin 2 928V DC
Figure 2.1: Starting up
Pin
Label
Description
1
GND
GND
2
VDD
VDD (+9V…+28V)
3
RS485+
RS485 interface, diff. signal (non-
inverting)
4
RS485-
RS485 interface, diff. signal (inverting)
5
IN_0
Digital input (+24V compatible)
Alternate function 1: step input
Alternate function 2: left stop switch
6
IN_1
Digital input (+24V compatible)
Alternate function 1: direction input
Alternate function 2: right stop switch
7
OUT_0 / IN_2
Open drain output with freewheeling
diode (max. 100mA)
Alternate function 1:
digital input (+24V compatible)
Alternate function 2:home switch
8
OUT_1 / IN_3
Open drain output with freewheeling
diode (max. 100mA)
Alternate function 1: digital input
(+24V compatible)
Alternate function 2: analog input
Connect momr Sw ch ON the power sugg 1 www.lrina micmm Insla g the TMCLVID m’ Came-2W! new” Lwe [nszaz/Rsoasmsalcummu v] Rszaz/Rsass Em: coma am 3600 Agdves: ‘ A IMCL lmggnud Devdopm EMMA-awm m [on mg mg [E Hap D BF] 5 “EVE Mons-- mum 3 (mm Module“ ,3 Send: Modulg. ux www. TRINAMICcom
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 7
www.trinamic.com
2. Connect motor
Pin
Label
Description
1
OB2
Pin 2 of motor coil B
2
OB1
Pin 1 of motor coil B
3
OA2
Pin 2 of motor coil A
4
OA1
Pin 1 of motor coil A
3. Switch ON the power supply
Turn power ON. The green LED for power lights up slowly and the motor is powered but in
standstill now.
If this does not occur, switch power OFF and check your connections as well as the power
supply.
2.1.2 Start the TMCL-IDE Software Development Environment
The TMCL-IDE is available on www.trinamic.com.
Installing the TMCL-IDE:
Make sure the COM port you intend to use is not blocked by another program.
Open TMCL-IDE by clicking TMCL.exe.
Choose Setup and Options and thereafter the Connection tab.
Choose COM port and type with the parameters shown in Figure 2.2 (baud rate 9600). Click OK.
Figure 2.2 Setup dialogue and connection tab of the TMCL-IDE.
Please refer to the TMCL-IDE User Manual for more information (see www.TRINAMIC.com).
—>. A mm D...“ Mod: rmcmrmn Q TMEL \mwcnnn Se‘eclnl lmlmdmn Mum / Bank laws 1 finnmmzngm v‘ J «(mums n MMmfl v, n a \ ileum: I: Cow m away Man-45‘ Imucnm mum 5m“ \gslmchnn ”we Mum/gank Va‘ge Diagam ‘ g D i U E} U U f; 010000000000000001 5mm 1 Amway Hm Tavgel Slalux mu Value wager" z o _. m www.m'namic com
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 8
www.trinamic.com
2.2 Using TMCL Direct Mode
1. Start TMCL Direct Mode.
Direct Mode
2. If the communication is established the TMCM-1021 is automatically detected. If the module is
not detected, please check all points above (cables, interface, power supply, COM port, baud
rate).
3. Issue a command by choosing Instruction, Type (if necessary), Motor, and Value and click
Execute to send it to the module.
Examples:
ROR rotate right, motor 0, value 10000 -> Click Execute. The first motor is rotating now.
MST motor stop, motor 0 -> Click Execute. The first motor stops now.
Top right of the TMCL Direct Mode window is the button Copy to editor. Click here to copy the chosen
command and create your own TMCL program. The command will be shown immediately on the editor.
NOTE
Please mind chapter 7 (programming techniques) of the TMCL-IDE User Manual on www.trinamic.com.
Here you will find information about creating general structures of TMCL programs. In particular
initialization, main loop, symbolic constants, variables, and subroutines are described there. Further you
can learn how to mix direct mode and stand alone mode.
Chapter 4.3 of this manual includes a diagram which points out the coolStep related axis parameters and
their functions. This can help you configuring your module to meet your needs.
w of E 255 E 255
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 9
www.trinamic.com
2.2.1 Important Motor Settings
There are some axis parameters which have to be adjusted right in the beginning after installing your
module. Please set the upper limiting values for the speed (axis parameter 4), the acceleration (axis
parameter 5), and the current (axis parameter 6). Further set the standby current (axis parameter 7) and
choose your microstep resolution with axis parameter 140. Please use the SAP (Set Axis Parameter)
command for adjusting these values. The SAP command is described in paragraph 3.5.5. You can use the
TMCM-IDE direct mode for easily configuring your module.
IMPORTANT AXIS PARAMETERS FOR MOTOR SETTING
Number
Axis Parameter
Description
Range [Unit]
4
Maximum
positioning
speed
Maximum feasible positioning speed. Has to be
adapted to motor and application
0… +268.435.454
[pps/s]
5
Maximum
acceleration
Limit for acceleration and deceleration. Has to be
adapted to motor and application.
1… +33554431
[pps/s]
6
Absolute max.
current
(CS / Current
Scale)
The maximum value is 255. This value means 100% of
maximum programmable current of the selected
motor current range (see axis parameter 179). Current
can be adjusted / scaled down by specifying a lower
value between 0 and 255. This value is transformed
into 32 different internal current settings supported by
the hardware (see hardware manual for more details
and complete table with possible current settings).
Please note: high current range is available for hardware
version V1.4, only!
0… 255
Low current range scaling
(axis parameter 179 set to
1):
  
 

  
 

High current range
scaling (axis parameter
179 set to 0):
  
 

  
 

7
Standby current
The current limit two seconds after the motor has
stopped.
0… 255
    

    

140
Microstep
resolution
0
full step
1
half step
2
4 microsteps
3
8 microsteps
4
16 microsteps
5
32 microsteps
6
64 microsteps
7
128 microsteps
8
256 microsteps
0… 8
ATTENTION
The most important motor setting is the absolute maximum motor current setting, since too high values
might cause motor damage!
3.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 10
www.trinamic.com
Number
Axis Parameter
Description
Range [Unit]
179
VSENSE
sense resistor voltage based current scaling
0: high current range up-to 1.4A RMS / 2A peak
1: low current range up-to 0.7A RMS / 1A peak
(default value)
Please note: this parameter should not and cannot
be changed for hardware V1.2! The high current
range is available for hardware V1.4, only!
0/1
2.3 Testing with a Simple TMCL Program
Type in the following program:
Assemble
Download Run
Stop
1. Click the Assemble icon to convert the TMCL into machine code.
2. Then download the program to the TMCM-1021 module by clicking the Download icon.
3. Press icon Run. The desired program will be executed.
4. Click the Stop button to stop the program.
ROL 0, 50000 //Rotate motor 0 with speed 50000
WAIT TICKS, 0, 500
MST 0
ROR 0, 50000 //Rotate motor 0 with 50000
WAIT TICKS, 0, 500
MST 0
SAP 4, 0, 50000 //Set max. Velocity
SAP 5, 0, 50000 //Set max. Acceleration
Loop: MVP ABS, 0, 100000 //Move to Position 100000
WAIT POS, 0, 0 //Wait until position reached
MVP ABS, 0, -100000 //Move to Position -100000
WAIT POS, 0, 0 //Wait until position reached
JA Loop //Infinite Loop
(hug/[www.tn na muccom
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 11
www.trinamic.com
3 TMCL and the TMCL-IDE: Introduction
As with most TRINAMIC modules the software running on the microprocessor of the TMCM-1061 consists
of two parts, a boot loader and the firmware itself. Whereas the boot loader is installed during
production and testing at TRINAMIC and remains untouched throughout the whole lifetime, the firmware
can be updated by the user. New versions can be downloaded free of charge from the TRINAMIC website
(http://www.trinamic.com).
The TMCM-1021 supports TMCL direct mode (binary commands) and standalone TMCL program execution.
You can store up to 876 TMCL instructions on it.
In direct mode and most cases the TMCL communication over RS485 follows a strict master/slave
relationship. That is, a host computer (e.g. PC/PLC) acting as the interface bus master will send a
command to the TMCL-1021. The TMCL interpreter on the module will then interpret this command, do
the initialization of the motion controller, read inputs and write outputs or whatever is necessary
according to the specified command. As soon as this step has been done, the module will send a reply
back over RS485 to the bus master. Only then should the master transfer the next command. Normally,
the module will just switch to transmission and occupy the bus for a reply, otherwise it will stay in
receive mode. It will not send any data over the interface without receiving a command first. This way,
any collision on the bus will be avoided when there are more than two nodes connected to a single bus.
The Trinamic Motion Control Language [TMCL] provides a set of structured motion control commands.
Every motion control command can be given by a host computer or can be stored in an EEPROM on the
TMCM module to form programs that run standalone on the module. For this purpose there are not only
motion control commands but also commands to control the program structure (like conditional jumps,
compare and calculating).
Every command has a binary representation and a mnemonic. The binary format is used to send
commands from the host to a module in direct mode, whereas the mnemonic format is used for easy
usage of the commands when developing standalone TMCL applications using the TMCL-IDE (IDE means
Integrated Development Environment).
There is also a set of configuration variables for the axis and for global parameters which allow
individual configuration of nearly every function of a module. This manual gives a detailed description of
all TMCL commands and their usage.
3.1 Binary Command Format
Every command has a mnemonic and a binary representation. When commands are sent from a host to a
module, the binary format has to be used. Every command consists of a one-byte command field, a one-
byte type field, a one-byte motor/bank field and a four-byte value field. So the binary representation of a
command always has seven bytes. When a command is to be sent via RS485 interface, it has to be
enclosed by an address byte at the beginning and a checksum byte at the end. In this case it consists of
nine bytes.
The binary command format for RS485 is as follows:
Bytes
Meaning
1
Module address
1
Command number
1
Type number
1
Motor or Bank number
4
Value (MSB first!)
1
Checksum
The checksum is calculated by adding up all the other bytes using an 8-bit addition.
Checksum calculalian
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 12
www.trinamic.com
Checksum calculation
As mentioned above, the checksum is calculated by adding up all bytes (including the module address
byte) using 8-bit addition. Here are two examples to show how to do this:
in C:
unsigned char i, Checksum;
unsigned char Command[9];
//Set the “Command” array to the desired command
Checksum = Command[0];
for(i=1; i<8; i++)
Checksum+=Command[i];
Command[8]=Checksum; //insert checksum as last byte of the command
//Now, send it to the module
in Delphi:
var
i, Checksum: byte;
Command: array[0..8] of byte;
//Set the “Command” array to the desired command
//Calculate the Checksum:
Checksum:=Command[0];
for i:=1 to 7 do Checksum:=Checksum+Command[i];
Command[8]:=Checksum;
//Now, send the “Command” array (9 bytes) to the module
3.2 Reply Format
Every time a command has been sent to a module, the module sends a reply.
The reply format for RS485 is as follows:
Bytes
Meaning
1
Reply address
1
Module address
1
Status (e.g. 100 means “no error”)
1
Command number
4
Value (MSB first!)
1
Checksum
The checksum is also calculated by adding up all the other bytes using an 8-bit addition.
Do not send the next command before you have received the reply!
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 13
www.trinamic.com
3.2.1 Status Codes
The reply contains a status code.
The status code can have one of the following values:
Code
Meaning
100
Successfully executed, no error
101
Command loaded into TMCL
program EEPROM
1
Wrong checksum
2
Invalid command
3
Wrong type
4
Invalid value
5
Configuration EEPROM locked
6
Command not available
3.3 Standalone Applications
The module is equipped with an EEPROM for storing TMCL applications. You can use TMCL-IDE for
developing standalone TMCL applications. You can load them down into the EEPROM and then it will run
on the module. The TMCL-IDE contains an editor and the TMCL assembler where the commands can be
entered using their mnemonic format. They will be assembled automatically into their binary
representations. Afterwards this code can be downloaded into the module to be executed there.
3.4 TMCL Command Overview
In this section a short overview of the TMCL commands is given.
3.4.1 TMCL Commands
Command
Number
Parameter
Description
ROR
1
<motor number>, <velocity>
Rotate right with specified velocity
ROL
2
<motor number>, <velocity>
Rotate left with specified velocity
MST
3
<motor number>
Stop motor movement
MVP
4
ABS|REL|COORD, <motor number>,
<position|offset>
Move to position (absolute or relative)
SAP
5
<parameter>, <motor number>, <value>
Set axis parameter (motion control
specific settings)
GAP
6
<parameter>, <motor number>
Get axis parameter (read out motion
control specific settings)
STAP
7
<parameter>, <motor number>
Store axis parameter permanently (non
volatile)
RSAP
8
<parameter>, <motor number>
Restore axis parameter
SGP
9
<parameter>, <bank number>, value
Set global parameter (module specific
settings e.g. communication settings
or TMCL user variables)
GGP
10
<parameter>, <bank number>
Get global parameter (read out module
specific settings e.g. communication
settings or TMCL user variables)
STGP
11
<parameter>, <bank number>
Store global parameter (TMCL user
variables only)
RSGP
12
<parameter>, <bank number>
Restore global parameter (TMCL user
variable only)
RFS
13
START|STOP|STATUS, <motor number>
Reference search
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 14
www.trinamic.com
Command
Number
Parameter
Description
SIO
14
<port number>, <bank number>, <value>
Set digital output to specified value
GIO
15
<port number>, <bank number>
Get value of analogue/digital input
CALC
19
<operation>, <value>
Process accumulator & value
COMP
20
<value>
Compare accumulator <-> value
JC
21
<condition>, <jump address>
Jump conditional
JA
22
<jump address>
Jump absolute
CSUB
23
<subroutine address>
Call subroutine
RSUB
24
Return from subroutine
EI
25
<interrupt number>
Enable interrupt
DI
26
<interrupt number>
Disable interrupt
WAIT
27
<condition>, <motor number>, <ticks>
Wait with further program execution
STOP
28
Stop program execution
SCO
30
<coordinate number>, <motor number>,
<position>
Set coordinate
GCO
31
<coordinate number>, <motor number>
Get coordinate
CCO
32
<coordinate number>, <motor number>
Capture coordinate
CALCX
33
<operation>
Process accumulator & X-register
AAP
34
<parameter>, <motor number>
Accumulator to axis parameter
AGP
35
<parameter>, <bank number>
Accumulator to global parameter
VECT
37
<interrupt number>, <label>
Set interrupt vector
RETI
38
Return from interrupt
ACO
39
<coordinate number>, <motor number>
Accu to coordinate
3.4.2 Commands Listed According to Subject Area
3.4.2.1 Motion Commands
These commands control the motion of the motor. They are the most important commands and can be
used in direct mode or in standalone mode.
Mnemonic
Command number
Meaning
ROL
2
Rotate left
ROR
1
Rotate right
MVP
4
Move to position
MST
3
Motor stop
RFS
13
Reference search
SCO
30
Store coordinate
CCO
32
Capture coordinate
GCO
31
Get coordinate
3.4.2.2 Parameter Commands
These commands are used to set, read and store axis parameters or global parameters. Axis parameters
can be set independently for each axis, whereas global parameters control the behavior of the module
itself. These commands can also be used in direct mode and in standalone mode.
Mnemonic
Command number
Meaning
SAP
5
Set axis parameter
GAP
6
Get axis parameter
STAP
7
Store axis parameter into EEPROM
RSAP
8
Restore axis parameter from EEPROM
SGP
9
Set global parameter
GGP
10
Get global parameter
STGP
11
Store global parameter into EEPROM
RSGP
12
Restore global parameter from EEPROM
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 15
www.trinamic.com
3.4.2.3 Control Commands
These commands are used to control the program flow (loops, conditions, jumps etc.). It does not make
sense to use them in direct mode. They are intended for standalone mode only.
Mnemonic
Command number
Meaning
JA
22
Jump always
JC
21
Jump conditional
COMP
20
Compare accumulator with constant
value
CSUB
23
Call subroutine
RSUB
24
Return from subroutine
WAIT
27
Wait for a specified event
STOP
28
End of a TMCL program
3.4.2.4 I/O Port Commands
These commands control the external I/O ports and can be used in direct mode and in standalone mode.
Mnemonic
Command number
Meaning
SIO
14
Set output
GIO
15
Get input
3.4.2.5 Calculation Commands
These commands are intended to be used for calculations within TMCL applications. Although they could
also be used in direct mode it does not make much sense to do so.
Mnemonic
Command number
Meaning
CALC
19
Calculate using the accumulator and a
constant value
CALCX
33
Calculate using the accumulator and the
X register
AAP
34
Copy accumulator to an axis parameter
AGP
35
Copy accumulator to a global parameter
ACO
39
Copy accu to coordinate
For calculating purposes there is an accumulator (or accu or A register) and an X register. When executed
in a TMCL program (in standalone mode), all TMCL commands that read a value store the result in the
accumulator. The X register can be used as an additional memory when doing calculations. It can be
loaded from the accumulator.
When a command that reads a value is executed in direct mode the accumulator will not be affected.
This means that while a TMCL program is running on the module (standalone mode), a host can still
send commands like GAP and GGP to the module (e.g. to query the actual position of the motor) without
affecting the flow of the TMCL program running on the module.
3.4.2.6 Interrupt Commands
Due to some customer requests, interrupt processing has been introduced in the TMCL firmware for ARM
based modules.
Mnemonic
Command number
Meaning
EI
25
Enable interrupt
DI
26
Disable interrupt
VECT
37
Set interrupt vector
RETI
38
Return from interrupt
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 16
www.trinamic.com
3.4.2.6.1 Interrupt Types
There are many different interrupts in TMCL, like timer interrupts, stop switch interrupts, position reached
interrupts, and input pin change interrupts. Each of these interrupts has its own interrupt vector. Each
interrupt vector is identified by its interrupt number. Please use the TMCL include file Interrupts.inc for
symbolic constants of the interrupt numbers.
3.4.2.6.2 Interrupt Processing
When an interrupt occurs and this interrupt is enabled and a valid interrupt vector has been defined for
that interrupt, the normal TMCL program flow will be interrupted and the interrupt handling routine will
be called. Before an interrupt handling routine gets called, the context of the normal program will be
saved automatically (i.e. accumulator register, X register, TMCL flags).
There is no interrupt nesting, i.e. all other interrupts are disabled while an interrupt handling routine is
being executed.
On return from an interrupt handling routine, the context of the normal program will automatically be
restored and the execution of the normal program will be continued.
3.4.2.6.3 Interrupt Vectors
The following table shows all interrupt vectors that can be used.
Interrupt number
Interrupt type
0
Timer 0
1
Timer 1
2
Timer 2
3
Target position reached
15
stallGuard2
21
Deviation
27
Left stop switch
28
Right stop switch
39
Input change 0
40
Input change 1
255
Global interrupts
3.4.2.6.4 Further Configuration of Interrupts
Some interrupts need further configuration (e.g. the timer interval of a timer interrupt). This can be done
using SGP commands with parameter bank 3 (SGP <type>, 3, <value>). Please refer to the SGP command
(paragraph 3.5.9) for further information about that.
3.4.2.6.5 Using Interrupts in TMCL
For using an interrupt proceed as follows:
- Define an interrupt handling routine using the VECT command.
- If necessary, configure the interrupt using an SGP <type>, 3, <value> command.
- Enable the interrupt using an EI <interrupt> command.
- Globally enable interrupts using an EI 255 command.
- An interrupt handling routine must always end with a RETI command
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 17
www.trinamic.com
The following example shows the use of a timer interrupt:
VECT 0, Timer0Irq //define the interrupt vector
SGP 0, 3, 1000 //configure the interrupt: set its period to 1000ms
EI 0 //enable this interrupt
EI 255 //globally switch on interrupt processing
//Main program: toggles output 1, using a WAIT command for the delay
Loop:
SIO 1, 2, 1
WAIT TICKS, 0, 50
SIO 1, 2, 0
WAIT TICKS, 0, 50
JA Loop
//Here is the interrupt handling routine
Timer0Irq:
GIO 0, 2 //check if OUT0 is high
JC NZ, Out0Off //jump if not
SIO 0, 2, 1 //switch OUT0 high
RETI //end of interrupt
Out0Off:
SIO 0, 2, 0 //switch OUT0 low
RETI //end of interrupt
In the example above, the interrupt numbers are used directly. To make the program better readable use
the provided include file Interrupts.inc. This file defines symbolic constants for all interrupt numbers
which can be used in all interrupt commands. The beginning of the program above then looks like the
following:
#include Interrupts.inc
VECT TI_TIMER0, Timer0Irq
SGP TI_TIMER0, 3, 1000
EI TI_TIMER0
EI TI_GLOBAL
Please also take a look at the other example programs.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 18
www.trinamic.com
3.5 Commands
The module specific commands are explained in more detail on the following pages. They are listed
according to their command number.
3.5.1 ROR (rotate right)
With this command the motor will be instructed to rotate with a specified velocity in positive direction
(increasing the position counter).
Like on all other TMCL modules, the motor will be accelerated or decelerated to the speed given with the
command. The speed is given in microsteps per second (pps). For conversion of this value into rounds
per minute etc. please refer to chapter 0, also.
The range is -268.435.455… +268.435.454.
Internal function: First, velocity mode is selected. Then, the velocity value is transferred to axis
parameter #0 (target velocity).
Related commands: ROL, MST, SAP, GAP
Mnemonic: ROR 0, <velocity>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
1
(don't care)
0*
<velocity>
-268.435.455… +268.435.454
*motor number is always O as the module supports just one axis
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Rotate right, velocity = 10000
Mnemonic: ROR 0, 10000
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$01
$00
$00
$00
$00
$27
$10
$39
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 19
www.trinamic.com
3.5.2 ROL (rotate left)
With this command the motor will be instructed to rotate with a specified velocity (opposite direction
compared to ROR, decreasing the position counter).
Like on all other TMCL modules, the motor will be accelerated or decelerated to the speed given with the
command. The speed is given in microsteps per second (pps). For conversion of this value into rounds
per minute etc. please refer to chapter 5.2, also.
The range is -268.435.455… +268.435.454.
Internal function: First, velocity mode is selected. Then, the velocity value is transferred to axis
parameter #0 (target velocity).
Related commands: ROR, MST, SAP, GAP
Mnemonic: ROL 0, <velocity>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
2
(don't care)
0*
<velocity>
-268.435.455… +268.435.454
* motor number is always O as the module supports just one axis
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Rotate left, velocity = 10000
Mnemonic: ROL 0, 10000
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$02
$00
$00
$00
$00
$27
$10
$3a
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 20
www.trinamic.com
3.5.3 MST (motor stop)
With this command the motor will be instructed to stop. The command uses the normal acceleration
parameter (soft stop / deceleration ramp possible).
Internal function: The axis parameter target velocity is set to zero.
Related commands: ROL, ROR, SAP, GAP
Mnemonic: MST 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
3
(don't care)
0*
(don't care)
* motor number is always O as the module support just one axis
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Stop motor
Mnemonic: MST 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$03
$00
$00
$00
$00
$00
$00
$04
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 21
www.trinamic.com
3.5.4 MVP (move to position)
With this command the motor will be instructed to move to a specified relative or absolute position or a
pre-programmed coordinate. It will use the acceleration/deceleration ramp and the positioning speed
programmed into the unit. This command is non-blocking that is, a reply will be sent immediately after
command interpretation and initialization of the motion controller. Further commands may follow
without waiting for the motor reaching its end position. The maximum velocity and acceleration are
defined by axis parameters #4 and #5.
The range of the MVP command is 32 bit signed (−2.147.483.648… +2.147.483.647). Positioning can be
interrupted using MST, ROL or ROR commands.
Attention:
Please note, that the distance between the actual position and the new one should not be more
than 2.147.483.647 (231-1) microsteps. Otherwise the motor will run in the opposite direction in
order to take the shorter distance.
Two operation types are available:
- Moving to an absolute position in the range from −2.147.483.648… +2.147.483.647 (-231 231-1).
- Starting a relative movement by means of an offset to the actual position. In this case, the new
resulting position value must not exceed the above mentioned limits, too.
Internal function: A new position value is transferred to the axis parameter #2 target position.
Related commands: SAP, GAP, SCO, CCO, GCO, MST
Mnemonic: MVP <ABS|REL|COORD>, 0, <position|offset|coordinate number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
4
0 ABS absolute
0*
<position>
−2.147.483.648…
+2.147.483.647
1 REL relative
0*
<offset>
−2.147.483.648…
+2.147.483.647
2 COORD
coordinate
0*
<coordinate number>
0… 20
*motor number is always O as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Move motor to (absolute) position 90000
Mnemonic: MVP ABS, 0, 90000
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$04
$00
$00
$00
$01
$5f
$90
$f5
Example:
Move motor from current position 10000 steps backward (move relative 10000)
Mnemonic: MVP REL, 0, -10000
Binary:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 22
www.trinamic.com
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$04
$01
$00
$ff
$ff
$d8
$f0
$cc
Example:
Move motor to previously stored coordinate #8
Mnemonic: MVP COORD, 0, 8
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$04
$02
$00
$00
$00
$00
$08
$0f
When moving to a coordinate, the coordinate has to be set properly in advance with the
help of the SCO, CCO or ACO command.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 23
www.trinamic.com
3.5.5 SAP (set axis parameter)
With this command most of the motion control parameters of the module can be specified. The settings
will be stored in SRAM and therefore, will be volatile. That is, information will be lost after power off.
Please use command STAP (store axis parameter) in order to store any setting permanently.
Internal function: The parameter format is converted ignoring leading zeros (or ones for negative
values). The parameter is transferred to the correct position in the appropriate device.
Related commands: GAP, STAP, RSAP, AAP
Mnemonic: SAP <parameter number>, 0, <value>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
5
<parameter
number>
0*
<value>
* motor number is always O as the module supports just one axis
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and values which can be used together with this command please refer to
chapter 4.
Example:
Set the absolute maximum current of the motor during movements to approx. 78% of max.
module
current:
Mnemonic: SAP 6, 0, 200
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$05
$06
$00
$00
$00
$00
$c8
$d4
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 24
www.trinamic.com
3.5.6 GAP (get axis parameter)
Most parameters of the TMCM-1021 can be adjusted individually for the axis. With this parameter they can
be read out. In standalone mode the requested value is also transferred to the accumulator register for
further processing purposes (such as conditioned jumps). In direct mode the value read is only output in
the value field of the reply (without affecting the accumulator).
Internal function: The parameter is read out of the correct position in the appropriate device. The
parameter format is converted adding leading zeros (or ones for negative values).
Related commands: SAP, STAP, AAP, RSAP
Mnemonic: GAP <parameter number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
6
<parameter number>
0*
(don't care)
*motor number is always O as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters which can be used together with this command please refer to chapter 4.
Example:
Get actual position of motor
Mnemonic: GAP 1, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$06
$01
$00
$00
$00
$00
$00
$08
Reply:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Host-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
$64
$06
$00
$00
$07
$d0
$44
Status = 100 (no error), position = 2000
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 25
www.trinamic.com
3.5.7 STAP (store axis parameter)
An axis parameter previously set with a Set Axis Parameter command (SAP) will be stored permanent.
Most parameters are automatically restored after power up.
Internal function: An axis parameter value stored in SRAM will be transferred to EEPROM and loaded
from EEPORM after next power up.
Related commands: SAP, RSAP, GAP, AAP
Mnemonic: STAP <parameter number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
7
<parameter number>
0*1
(don't care)*2
*1motor number is always O as only one motor is involved
*2the value operand of this function has no effect. Instead, the current setting (e.g. previously set with SAP) is saved.
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Parameter ranges:
Parameter number
Motor number
Value
s. chapter 4
0
s. chapter 4
For a table with parameters which can be used together with this command please refer to chapter 4.
Example:
Store the maximum speed of motor
Mnemonic: STAP 4, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$07
$04
$00
$00
$00
$00
$00
$0c
Note: The STAP command will not have any effect when the configuration EEPROM is locked (refer to
5.1). In direct mode, the error code 5 (configuration EEPROM locked, see also section 0) will be
returned in this case.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 26
www.trinamic.com
3.5.8 RSAP (restore axis parameter)
For all configuration-related axis parameters non-volatile memory locations are provided. By default, most
parameters are automatically restored after power up. A single parameter that has been changed before
can be reset by this instruction also.
Internal function: The specified parameter is copied from the configuration EEPROM memory to its RAM
location.
Relate commands: SAP, STAP, GAP, and AAP
Mnemonic: RSAP <parameter number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
8
<parameter number>
0*
(don't care)
*motor number is always O as only one motor is involved
Reply structure in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters which can be used together with this command please refer to chapter 4.
Example:
Restore the maximum current of motor
Mnemonic: RSAP 6, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$08
$06
$00
$00
$00
$00
$00
$0f
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 27
www.trinamic.com
3.5.9 SGP (set global parameter)
With this command most of the module specific parameters not directly related to motion control can be
specified and the TMCL user variables can be changed. Global parameters are related to the host
interface, peripherals or application specific variables. The different groups of these parameters are
organized in banks to allow a larger total number for future products. Currently, only bank 0 and 1 are
used for global parameters, and bank 2 is used for user variables.
All module settings will automatically be stored non-volatile (internal EEPROM of the processor). The
TMCL user variables will not be stored in the EEPROM automatically, but this can be done by using
STGP commands.
Internal function: the parameter format is converted ignoring leading zeros (or ones for negative
values). The parameter is transferred to the correct position in the appropriate (on board) device.
Related commands: GGP, STGP, RSGP, AGP
Mnemonic: SGP <parameter number>, <bank number>, <value>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
9
<parameter number>
<bank number>
<value>
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and bank numbers which can be used together with this command please
refer to chapter 5.
Example:
Set the serial address of the target device (module) to 3
Mnemonic: SGP 66, 0, 3
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$09
$42
$00
$00
$00
$00
$03
$4f
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 28
www.trinamic.com
3.5.10 GGP (get global parameter)
All global parameters can be read with this function. Global parameters are related to the host interface,
peripherals or application specific variables. The different groups of these parameters are organized in
banks to allow a larger total number for future products. Currently, only bank 0 and 1 are used for global
parameters, and bank 2 is used for user variables.
Internal function: the parameter is read out of the correct position in the appropriate device. The
parameter format is converted adding leading zeros (or ones for negative values).
Related commands: SGP, STGP, RSGP, AGP
Mnemonic: GGP <parameter number>, <bank number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
10
<parameter number>
<bank number>
(don't care)
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and bank numbers which can be used together with this command please
refer to chapter 5.
Example:
Get the serial address of the target device
Mnemonic: GGP 66, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0a
$42
$00
$00
$00
$00
$00
$4d
Reply:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Host-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
$64
$0a
$00
$00
$00
$01
$72
Status = 100 (no error), Value = 1
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 29
www.trinamic.com
3.5.11 STGP (store global parameter)
This command is used to store TMCL user variables permanently in the EEPROM of the module. Some
global parameters are located in RAM memory, so without storing them any modification will be lost at
power down. This instruction enables permanent storing. Most parameters are automatically restored
after power up.
Internal function: the specified parameter will be copied from its RAM location to the configuration
EEPROM.
Related commands: SGP, GGP, RSGP, AGP
Mnemonic: STGP <parameter number>, <bank number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
11
<parameter number>
<bank number>
(don't care)
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and bank numbers which can be used together with this command please
refer to chapter 5.
Example:
Store user variable #42
Mnemonic: STGP 42, 2
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0b
$2a
$02
$00
$00
$00
$00
$38
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 30
www.trinamic.com
3.5.12 RSGP (restore global parameter)
With this command the contents of a TMCL user variable can be restored from the EEPROM. By default,
most parameters are automatically restored after power up. A single parameter that has been changed
before can be reset by this instruction.
Internal function: the specified parameter is copied from the configuration EEPROM memory to its RAM
location.
Relate commands: SGP, STGP, GGP, and AGP
Mnemonic: RSAP <parameter number>, <bank number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
12
<parameter number>
<bank number>
(don't care)
Reply structure in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and bank numbers which can be used together with this command please
refer to chapter 5.
Example:
Restore user variable #42
Mnemonic: RSGP 42, 2
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0c
$2a
$02
$00
$00
$00
$00
$39
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 31
www.trinamic.com
3.5.13 RFS (reference search)
The TMCL firmware has a built-in reference search algorithm which can be used. The reference search
algorithm provides switching point calibration and three switch modes. The status of the reference
search can also be queried to see if it has already finished. Please see the appropriate parameters in the
axis parameter table to configure the reference search algorithm to meet your needs (chapter 4). The
reference search can be started, stopped, and the actual status of the reference search can be checked.
Internal function: The reference search is implemented as a state machine, so interaction is possible
during execution.
Related commands: WAIT
Mnemonic: RFS <START|STOP|STATUS>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
13
0 START start ref. search
1 STOP abort ref. search
2 STATUS get status
0*
(don't care)
*motor number is always O as only one motor is involved
Reply in direct mode:
When using type 0 (START) or 1 (STOP):
STATUS
VALUE
100 OK
(don't care)
When using type 2 (STATUS):
STATUS
VALUE
100 OK
0 no ref. search active
other values ref.
search is active
Example:
Start reference search of motor
Mnemonic: RFS START, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0d
$00
$00
$00
$00
$00
$00
$0f
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 32
www.trinamic.com
3.5.14 SIO (set output)
This command sets the status of the general digital output either to low (0) or to high (1).
Internal function: the passed value is transferred to the specified output line.
Related commands: GIO, WAIT
Mnemonic: SIO <port number>, <bank number>, <value>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
14
<port number>
<bank number>
<value>
Reply structure:
STATUS
VALUE
100 OK
(don't care)
Example:
Set OUT_1 to high (bank 2, output 1; general purpose output)
Mnemonic: SIO 1, 2, 1
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0e
$01
$02
$00
$00
$00
$01
$13
I/O pin definition
Power / communication / I/Os
18
Figure 3.1: I/O connector of TMCM-1021
Please note, that the module has four I/O pins
including two open drain outputs:
Pin 7: OUT_0 (open collector)
Pin 8: OUT_1 (open collector)
Please refer to the Hardware Manual for further
information.
Addressinq both output lines with an: 510 command: The followmu Dloqram wxll show the states of the Input [mes on the output lines:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 33
www.trinamic.com
Available I/O ports of TMCM-1021:
Pin
I/O port
Command
Range <n>
7
OUT_0
SIO 0, 2, <n>
1/0
8
OUT_1
SIO 1, 2, <n>
1/0
Addressing both output lines with one SIO command:
Set the type parameter to 255 and the bank parameter to 2.
The value parameter must then be set to a value between 0… 255, where every bit represents
one output line.
Furthermore, the value can also be set to -1. In this special case, the contents of the lower 8 bits
of the accumulator are copied to the output pins.
Example:
Set both output pins high.
Mnemonic: SIO 255, 2, 127
The following program will show the states of the input lines on the output lines:
Loop: GIO 255, 0
SIO 255, 2,-1
JA Loop
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 34
www.trinamic.com
3.5.15 GIO (get input/output)
With this command the status of the available general purpose inputs of the module can be read out.
The function reads a digital or analogue input port. Digital lines will be read as 0 or 1, while the ADC
channels deliver their 12bit result in the range of 0 4095. In standalone mode the requested value is
copied to the accumulator (accu) for further processing purposes such as conditional jumps. In direct
mode the value is only output in the value field of the reply, without affecting the accumulator. The
actual status of a digital output line can also be read.
Internal function: the specified signal pin is read.
Related commands: SIO, WAIT
Mnemonic: GIO <port number>, <bank number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
15
<port number>
<bank number>
(don't care)
Reply in direct mode:
STATUS
VALUE
100 OK
<status of the
port>
Example:
Get the analogue value of IN_3
Mnemonic: GIO 3, 1
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0f
$03
$01
$00
$00
$00
$00
$14
Reply:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Host-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
$64
$0f
$00
$00
$01
$fa
$72
value: 506
Reading all digital inputs with one 610 command: Use followina Drouram to renresent the states of the input lines on the output lines:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 35
www.trinamic.com
I/O pin definition
Power / communication / I/Os
18
Figure 3.2: I/O connector of TMCM-1021
3.5.15.1 I/O bank 0 digital inputs:
IN_3 can be read as digital or analogue input. The analogue values can be accessed in bank 1.
Reading all digital inputs with one GIO command:
Set the type parameter to 255 and the bank parameter to 0.
In this case the status of all digital input lines will be read to the lower eight bits of the
accumulator.
Use following program to represent the states of the input lines on the output lines:
Loop: GIO 255, 0
SIO 255, 2,-1
JA Loop
3.5.15.2 I/O bank 1 analogue input:
IN_3 can be read back as digital or analogue input. The digital states can be accessed in bank 0.
3.5.15.3 I/O bank 2 the states of digital outputs
The states of the OUT lines (that have been set by SIO commands) can be read back using bank 2.
Pin
I/O port
Command
Result range
5
IN_0
GIO 0, 0
0/1
6
IN_1
GIO 1, 0
0/1
7
IN_2 (same pin as OUT_0)
GIO 2, 0
0/1
8
IN_3 (same pin as OUT_1)
GIO 3, 0
0/1
Pin
I/O port
Command
Result range
8
IN_3 (same pin as OUT_1)
GIO 3, 1
0… 4095
Pin
I/O port
Command
Result range
7
OUT_0
GIO 0, 2
0/1
8
OUT_1
GIO 1, 2
0/1
Please note, that the module has four I/O pins
including four input pins:
Pin 5: IN_O (digital)
Pin 6: IN_1 (digital)
Pin 7: IN_2 (digital)
Pin 8: IN_3 (digital or analog)
Please refer to the Hardware Manual for further
information.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 36
www.trinamic.com
3.5.16 CALC (calculate)
A value in the accumulator variable, previously read by a function such as GAP (get axis parameter) can
be modified with this instruction. Nine different arithmetic functions can be chosen and one constant
operand value must be specified. The result is written back to the accumulator, for further processing like
comparisons or data transfer.
Related commands: CALCX, COMP, JC, AAP, AGP, GAP, GGP, GIO
Mnemonic: CALC <operation>, <value>
where <op> is ADD, SUB, MUL, DIV, MOD, AND, OR, XOR, NOT or LOAD
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
19
0 ADD add to accu
1 SUB subtract from accu
2 MUL multiply accu by
3 DIV divide accu by
4 MOD modulo divide by
5 AND logical and accu with
6 OR logical or accu with
7 XOR logical exor accu with
8 NOT logical invert accu
9 LOAD load operand to accu
(don't care)
<operand>
Example:
Multiply accu by -5000
Mnemonic: CALC MUL, -5000
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$13
$02
$00
$FF
$FF
$EC
$78
$78
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 37
www.trinamic.com
3.5.17 COMP (compare)
The specified number is compared to the value in the accumulator register. The result of the comparison
can for example be used by the conditional jump (JC) instruction. This command is intended for use in
standalone operation only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode.
Internal function: the specified value is compared to the internal "accumulator", which holds the value
of a preceding "get" or calculate instruction (see GAP/GGP/GIO/CALC/CALCX). The internal arithmetic status
flags are set according to the comparison result.
Related commands: JC (jump conditional), GAP, GGP, GIO, CALC, CALCX
Mnemonic: COMP <value>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
20
(don't care)
(don't care)
<comparison value>
Example:
Jump to the address given by the label when the position of motor is greater than or equal to
1000.
GAP 1, 2, 0 //get axis parameter, type: no. 1 (actual position), motor: 0, value: 0 (don't care)
COMP 1000 //compare actual value to 1000
JC GE, Label //jump, type: 5 greater/equal, the label must be defined somewhere else in the
program
Binary format of the COMP 1000 command:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$14
$00
$00
$00
$00
$03
$e8
$00
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 38
www.trinamic.com
3.5.18 JC (jump conditional)
The JC instruction enables a conditional jump to a fixed address in the TMCL program memory, if the
specified condition is met. The conditions refer to the result of a preceding comparison. Please refer to
COMP instruction for examples. This function is for standalone operation only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode. See the host-only control functions for details.
Internal function: the TMCL program counter is set to the passed value if the arithmetic status flags are
in the appropriate state(s).
Related commands: JA, COMP, WAIT, CLE
Mnemonic: JC <condition>, <label>
where <condition>=ZE|NZ|EQ|NE|GT|GE|LT|LE|ETO|EAL|EDV|EPO
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
21
0 ZE - zero
1 NZ - not zero
2 EQ - equal
3 NE - not equal
4 GT - greater
5 GE - greater/equal
6 LT - lower
7 LE - lower/equal
8 ETO - time out error
(don't care)
<jump address>
Example:
Jump to address given by the label when the position of motor is greater than or equal to 1000.
GAP 1, 0, 0 //get axis parameter, type: no. 1 (actual position), motor: 0, value: 0 (don't care)
COMP 1000 //compare actual value to 1000
JC GE, Label //jump, type: 5 greater/equal
...
...
Label: ROL 0, 1000
Binary format of JC GE, Label when Label is at address 10:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$15
$05
$00
$00
$00
$00
$0a
$25
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 39
www.trinamic.com
3.5.19 JA (jump always)
Jump to a fixed address in the TMCL program memory. This command is intended for standalone
operation only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode.
Internal function: the TMCL program counter is set to the passed value.
Related commands: JC, WAIT, CSUB
Mnemonic: JA <Label>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
22
(don't care)
(don't care)
<jump address>
Example:
An infinite loop in TMCL™
Loop: MVP ABS, 0, 10000
WAIT POS, 0, 0
MVP ABS, 0, 0
WAIT POS, 0, 0
JA Loop //Jump to the label Loop
Binary format of JA Loop assuming that the label Loop is at address 20:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$16
$00
$00
$00
$00
$00
$14
$2b
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 40
www.trinamic.com
3.5.20 CSUB (call subroutine)
This function calls a subroutine in the TMCL program memory. It is intended for standalone operation
only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode.
Internal function: the actual TMCL program counter value is saved to an internal stack, afterwards
overwritten with the passed value. The number of entries in the internal stack is limited to 8. This also
limits nesting of subroutine calls to 8. The command will be ignored if there is no more stack space left.
Related commands: RSUB, JA
Mnemonic: CSUB <Label>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
23
(don't care)
(don't care)
<subroutine address>
Example:
Call a subroutine
Loop: MVP ABS, 0, 10000
CSUB SubW //Save program counter and jump to label “SubW”
MVP ABS, 0, 0
JA Loop
SubW: WAIT POS, 0, 0
WAIT TICKS, 0, 50
RSUB //Continue with the command following the CSUB command
Binary format of the CSUB SubW command assuming that the label SubW is at address 100:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$17
$00
$00
$00
$00
$00
$64
$7c
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 41
www.trinamic.com
3.5.21 RSUB (return from subroutine)
Return from a subroutine to the command after the CSUB command. This command is intended for use
in standalone mode only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode.
Internal function: the TMCL program counter is set to the last value of the stack. The command will be
ignored if the stack is empty.
Related command: CSUB
Mnemonic: RSUB
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
24
(don't care)
(don't care)
(don't care)
Example: please see the CSUB example (section 3.5.20).
Binary format of RSUB:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$18
$00
$00
$00
$00
$00
$00
$19
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 42
www.trinamic.com
3.5.22 WAIT (wait for an event to occur)
This instruction interrupts the execution of the TMCL program until the specified condition is met. This
command is intended for standalone operation only.
The host address and the reply are only used to take the instruction to the TMCL program memory
while the program is being downloaded. It does not make sense to use this command in direct
mode.
There are five different wait conditions that can be used:
TICKS: Wait until the number of timer ticks specified by the <ticks> parameter has been
reached.
POS: Wait until the target position of the motor specified by the <motor> parameter has been
reached. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
REFSW: Wait until the reference switch of the motor specified by the <motor> parameter has
been triggered. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
LIMSW: Wait until a limit switch of the motor specified by the <motor> parameter has been
triggered. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
RFS: Wait until the reference search of the motor specified by the <motor> field has been
reached. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
The timeout flag (ETO) will be set after a timeout limit has been reached. You can then use a JC ETO
command to check for such errors or clear the error using the CLE command.
Internal function: the TMCL program counter is held until the specified condition is met.
Related commands: JC, CLE
Mnemonic: WAIT <condition>, <motor>, <ticks>
where <condition> is TICKS|POS|REFSW|LIMSW|RFS
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
27
0 TICKS - timer ticks*1
don’t care
<no. of ticks*2>
1 POS - target position reached
0*1
<no. of ticks* for timeout>,
0 for no timeout
2 REFSW reference switch
0
<no. of ticks* for timeout>,
0 for no timeout
3 LIMSW limit switch
0
<no. of ticks* for timeout>,
0 for no timeout
4 RFS reference search
completed
0
<no. of ticks* for timeout>,
0 for no timeout
*1 motor number is always 0 as only one motor is involved
*2 one tick is 10 milliseconds
Example:
Wait for motor to reach its target position, without timeout
Mnemonic: WAIT POS, 0, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1b
$01
$00
$00
$00
$00
$00
$1e
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 43
www.trinamic.com
3.5.23 STOP (stop TMCL program execution)
This function stops executing a TMCL program. The host address and the reply are only used to transfer
the instruction to the TMCL program memory.
This command should be placed at the end of every standalone TMCL program. It is not to be used
in direct mode.
Internal function: TMCL instruction fetching is stopped.
Related commands: none
Mnemonic: STOP
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
28
(don't care)
(don't care)
(don't care)
Example:
Mnemonic: STOP
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1c
$00
$00
$00
$00
$00
$00
$1d
These SDECIal funmons (an be accessed usmq the followmq specuaL forms of the SCO command:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 44
www.trinamic.com
3.5.24 SCO (set coordinate)
Up to 20 position values (coordinates) can be stored for every axis for use with the MVP COORD
command. This command sets a coordinate to a specified value. Depending on the global parameter 84,
the coordinates are only stored in RAM or also stored in the EEPROM and copied back on startup (with
the default setting the coordinates are stored in RAM only).
Please note that the coordinate number 0 is always stored in RAM only.
Internal function: the passed value is stored in the internal position array.
Related commands: GCO, CCO, MVP
Mnemonic: SCO <coordinate number>, 0, <position>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
30
<coordinate number>
(0… 20)
0*
<position>
(-223…+223)
* Motor number is always 0 as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Set coordinate #1 of motor to 1000
Mnemonic: SCO 1, 0, 1000
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1e
$01
$00
$00
$00
$03
$e8
$0d
Two special functions of this command have been introduced that make it possible to copy all
coordinates or one selected coordinate to the EEPROM.
These special functions can be accessed using the following special forms of the SCO command:
SCO 0, 255, 0 copies all coordinates (except coordinate number 0) from RAM to
the EEPROM.
SCO <coordinate number>, 255, 0 copies the coordinate selected by <coordinate number> to the
EEPROM. The coordinate number must be a value between 1 and
20.
These SDECIal functxons (an be accessed usmq the followmq Spemal forms of the GCO command:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 45
www.trinamic.com
3.5.25 GCO (get coordinate)
This command makes possible to read out a previously stored coordinate. In standalone mode the
requested value is copied to the accumulator register for further processing purposes such as
conditioned jumps. In direct mode, the value is only output in the value field of the reply, without
affecting the accumulator. Depending on the global parameter 84, the coordinates are only stored in RAM
or also stored in the EEPROM and copied back on startup (with the default setting the coordinates are
stored in RAM only).
Please note that the coordinate number 0 is always stored in RAM only.
Internal function: the desired value is read out of the internal coordinate array, copied to the
accumulator register and -in direct mode- returned in the “value” field of the reply.
Related commands: SCO, CCO, MVP
Mnemonic: GCO <coordinate number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
31
<coordinate number>
(0… 20)
0*
(don't care)
* Motor number is always 0 as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Get motor value of coordinate 1
Mnemonic: GCO 1, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1f
$01
$00
$00
$00
$00
$00
$23
Reply:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
$64
$0a
$00
$00
$00
$00
$86
Value: 0
Two special functions of this command have been introduced that make it possible to copy all
coordinates or one selected coordinate from the EEPROM to the RAM.
These special functions can be accessed using the following special forms of the GCO command:
GCO 0, 255, 0 copies all coordinates (except coordinate number 0) from the
EEPROM to the RAM.
GCO <coordinate number>, 255, 0 copies the coordinate selected by <coordinate number> from the
EEPROM to the RAM. The coordinate number must be a value
between 1 and 20.
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 46
www.trinamic.com
3.5.26 CCO (capture coordinate)
The actual position of the axis is copied to the selected coordinate variable. Depending on the global
parameter 84, the coordinates are only stored in RAM or also stored in the EEPROM and copied back on
startup (with the default setting the coordinates are stored in RAM only). Please see the SCO and GCO
commands on how to copy coordinates between RAM and EEPROM.
Note that the coordinate number 0 is always stored in RAM only.
Internal function: the selected (24 bit) position values are written to the 20 by 3 bytes wide coordinate
array.
Related commands: SCO, GCO, MVP
Mnemonic: CCO <coordinate number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
32
<coordinate number>
0… 20
0*
(don't care)
* Motor number is always 0 as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Store current position of the axe to coordinate 3
Mnemonic: CCO 3, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$20
$03
$00
$00
$00
$00
$00
$2b
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 47
www.trinamic.com
3.5.27 ACO
With the ACO command the actual value of the accumulator is copied to a selected coordinate of the
motor. Depending on the global parameter 84, the coordinates are only stored in RAM or also stored in
the EEPROM and copied back on startup (with the default setting the coordinates are stored in RAM only).
Please note also that the coordinate number 0 is always stored in RAM only. For Information about
storing coordinates refer to the SCO command.
Internal function: the actual value of the accumulator is stored in the internal position array.
Related commands: GCO, CCO, MVP COORD, SCO
Mnemonic: ACO <coordinate number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
39
<coordinate number>
0… 20
0*
(don’t care)
* Motor number is always 0 as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
Example:
Copy the actual value of the accumulator to coordinate 1 of motor
Mnemonic: ACO 1, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$27
$01
$00
$00
$00
$00
$00
$29
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 48
www.trinamic.com
3.5.28 CALCX (calculate using the X register)
This instruction is very similar to CALC, but the second operand comes from the X register. The X register
can be loaded with the LOAD or the SWAP type of this instruction. The result is written back to the
accumulator for further processing like comparisons or data transfer.
Related commands: CALC, COMP, JC, AAP, AGP
Mnemonic: CALCX <operation>
with <operation>=ADD|SUB|MUL|DIV|MOD|AND|OR|XOR|NOT|LOAD|SWAP
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
33
0 ADD add X register to accu
1 SUB subtract X register from accu
2 MUL multiply accu by X register
3 DIV divide accu by X-register
4 MOD modulo divide accu by x-register
5 AND logical and accu with X-register
6 OR logical or accu with X-register
7 XOR logical exor accu with X-register
8 NOT logical invert X-register
9 LOAD load accu to X-register
10 SWAP swap accu with X-register
(don't care)
(don't care)
Example:
Multiply accu by X-register
Mnemonic: CALCX MUL
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$21
$02
$00
$00
$00
$00
$00
$24
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 49
www.trinamic.com
3.5.29 AAP (accumulator to axis parameter)
The content of the accumulator register is transferred to the specified axis parameter. For practical usage,
the accumulator has to be loaded e.g. by a preceding GAP instruction. The accumulator may have been
modified by the CALC or CALCX (calculate) instruction.
Related commands: AGP, SAP, GAP, SGP, GGP, GIO, GCO, CALC, CALCX
Mnemonic: AAP <parameter number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
34
<parameter number>
0*
<don't care>
* Motor number is always 0 as only one motor is involved
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and values which can be used together with this command please refer to
chapter 5.
Example:
Positioning motor by a potentiometer connected to the analogue input #0:
Start: GIO 0,1 // get value of analogue input line 0
CALC MUL, 4 // multiply by 4
AAP 0,0 // transfer result to target position of motor 0
JA Start // jump back to start
Binary format of the AAP 0,0 command:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$22
$00
$00
$00
$00
$00
$00
$23
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 50
www.trinamic.com
3.5.30 AGP (accumulator to global parameter)
The content of the accumulator register is transferred to the specified global parameter. For practical
usage, the accumulator has to be loaded e.g. by a preceding GGP instruction. The accumulator may have
been modified by the CALC or CALCX (calculate) instruction.
Related commands: SGP, GGP, STGP, RSGP
Mnemonic: AGP <parameter number>, <bank number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
35
<parameter number>
<bank number>
(don't care)
Reply in direct mode:
STATUS
VALUE
100 OK
(don't care)
For a table with parameters and bank numbers which can be used together with this command please
refer to chapter 5.
Example:
Copy accumulator to TMCL user variable #3
Mnemonic: AGP 3, 2
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$23
$03
$02
$00
$00
$00
$00
$29
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 51
www.trinamic.com
3.5.31 CLE (clear error flags)
This command clears the internal error flags. It is intended for use in standalone mode only and must
not be used in direct mode.
The following error flags can be cleared by this command (determined by the <flag> parameter):
ALL: clear all error flags.
ETO: clear the timeout flag.
EAL: clear the external alarm flag
EDV: clear the deviation flag
EPO: clear the position error flag
Related commands: JC
Mnemonic: CLE <flags>
where <flags>=ALL|ETO|EDV|EPO
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
36
0 (ALL) all flags
1 (ETO) timeout flag
2 (EAL) alarm flag
3 (EDV) deviation flag
4 (EPO) position flag
5 (ESD) shutdown flag
(don't care)
(don't care)
Example:
Reset the timeout flag
Mnemonic: CLE ETO
Binary:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$24
$01
$00
$00
$00
$00
$00
$26
The followmu table shows all Interrupt vectors that can be used:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 52
www.trinamic.com
3.5.32 VECT (set interrupt vector)
The VECT command defines an interrupt vector. It needs an interrupt number and a label as parameter
(like in JA, JC and CSUB commands).
This label must be the entry point of the interrupt handling routine.
Related commands: EI, DI, RETI
Mnemonic: VECT <interrupt number>, <label>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
37
<interrupt number>
(don't care)
<label>
The following table shows all interrupt vectors that can be used:
Interrupt number
Interrupt type
0
Timer 0
1
Timer 1
2
Timer 2
3
(Target) position reached
15
Stall (stallGuard2)
21
Deviation
27
Stop left
28
Stop right
39
IN_0 change
40
IN_1 change
Example: Define interrupt vector at target position 500
VECT 3, 500
Binary format of VECT:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$25
$03
$00
$00
$00
$01
$F4
$1E
The followmu table shows all Interrupt vectors that can be used:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 53
www.trinamic.com
3.5.33 EI (enable interrupt)
The EI command enables an individual interrupt and activates interrupts in general (global interrupt
enable). Please make sure to always issue a global interrupt enable in order to actually activate the
interrupts individually enabled.
Related command: DI, VECT, RETI
Mnemonic: EI <interrupt number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
25
<interrupt number>
(don't care)
(don't care)
The following table shows all interrupt vectors that can be used:
Interrupt number
Interrupt type
0
Timer 0
1
Timer 1
2
Timer 2
3
(Target) position reached
15
Stall (stallGuard2)
21
Deviation
27
Stop left
28
Stop right
39
IN_0 change
40
IN_1 change
255
Global interrupts
Examples:
Enable interrupts globally
EI, 255
Binary format of EI:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$19
$FF
$00
$00
$00
$00
$00
$19
Enable interrupt when target position reached
EI, 3
Binary format of EI:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$19
$03
$00
$00
$00
$00
$00
$1D
The followmu table shows all Interrupt vectors that can be used:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 54
www.trinamic.com
3.5.34 DI (disable interrupt)
The DI command disables an individual interrupt or using parameter 255 will de-activate any interrupt.
Related command: EI, VECT, RETI
Mnemonic: DI <interrupt number>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
26
<interrupt number>
(don't care)
(don't care)
The following table shows all interrupt vectors that can be used:
Interrupt number
Interrupt type
0
Timer 0
1
Timer 1
2
Timer 2
3
(Target) position reached
15
Stall (stallGuard2)
21
Deviation
39
IN_0 change
40
IN_1 change
255
Global interrupts
Examples:
Disable interrupts globally
DI, 255
Binary format of DI:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1A
$FF
$00
$00
$00
$00
$00
$1A
Disable interrupt when target position reached
DI, 3
Binary format of DI:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$1A
$03
$00
$00
$00
$00
$00
$1E
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 55
www.trinamic.com
3.5.35 RETI (return from interrupt)
This command terminates the interrupt handling routine, and the normal program execution continues.
At the end of an interrupt handling routine the RETI command must be executed.
Internal function: the saved registers (A register, X register, flags) are copied back. Normal program
execution continues.
Related commands: EI, DI, VECT
Mnemonic: RETI
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
38
(don’t care)
(don't care)
(don’t care)
Example: Terminate interrupt handling and continue with normal program execution
RETI
Binary format of RETI:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$26
$00
$00
$00
$00
$00
$00
$27
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 56
www.trinamic.com
3.5.36 Customer Specific TMCL Command Extension (UF0 UF7/user
function)
The user definable functions UF0… UF7 are predefined functions for user specific purposes. Contact
TRINAMIC for the customer specific programming of these functions.
Internal function: call user specific functions implemented in C by TRINAMIC.
Related commands: none
Mnemonic: UF0 UF7
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
64… 71
(user defined)
(user defined)
(user defined)
Reply in direct mode:
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
(user
defined)
64… 71
(user
defined)
(user
defined)
(user
defined)
(user
defined)
<checksum>
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 57
www.trinamic.com
3.5.37 Request Target Position Reached Event
This command is the only exception to the TMCL protocol, as it sends two replies: One immediately after
the command has been executed (like all other commands also), and one additional reply that will be
sent when the motor has reached its target position. This instruction can only be used in direct mode
(in standalone mode, it is covered by the WAIT command) and hence does not have a mnemonic.
Internal function: send an additional reply when the motor has reached its target position
Mnemonic: ---
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
138
(don’t care)
(don’t care)
0*
* Motor number
Reply in direct mode (right after execution of this command):
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
100
138
$00
$00
$00
Motor bit
mask
<checksum
>
Additional reply in direct mode (after motors have reached their target positions):
Byte Index
0
1
2
3
4
5
6
7
8
Function
Target-
address
Target-
address
Status
Instruction
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$02
$01
128
138
$00
$00
$00
Motor bit
mask
<checksum
>
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 58
www.trinamic.com
3.5.38 TMCL Control Functions
The following functions are for host control purposes only and are not allowed for standalone
mode. In most cases, there is no need for the customer to use one of those functions (except
command 139). They are mentioned here only for reasons of completeness. These commands have no
mnemonics, as they cannot be used in TMCL programs. The Functions are to be used only by the TMCL-
IDE to communicate with the module, for example to download a TMCL application into the module.
The only control commands that could be useful for a user host application are:
- get firmware revision (command 136, please note the special reply format of this command,
described at the end of this section)
- run application (command 129)
All other functions can be achieved by using the appropriate functions of the TMCL-IDE.
Instruction
Description
Type
Mot/Bank
Value
128 stop application
a running TMCL standalone
application is stopped
(don't care)
(don't care)
(don't care)
129 run application
TMCL execution is started (or
continued)
0 - run from current
address
1 - run from
specified address
(don't care)
(don't care)
starting address
130 step application
only the next command of a TMCL
application is executed
(don't care)
(don't care)
(don't care)
131 reset application
the program counter is set to
zero, and the standalone
application is stopped (when
running or stepped)
(don't care)
(don't care)
(don't care)
132 start download
mode
target command execution is
stopped and all following
commands are transferred to the
TMCL memory
(don't care)
(don't care)
starting address
of the
application
133 quit download
mode
target command execution is
resumed
(don't care)
(don't care)
(don't care)
134 read TMCL
memory
the specified program memory
location is read
(don't care)
(don't care)
<memory
address>
135 get application
status
one of these values is returned:
0 stop
1 run
2 step
3 reset
(don't care)
(don't care)
(don't care)
136 get firmware
version
return the module type and
firmware revision either as a
string or in binary format
0 string
1 binary
(don’t care)
(don’t care)
137 restore factory
settings
reset all settings stored in the
EEPROM to their factory defaults
This command does not send back
a reply.
(don’t care)
(don’t care)
must be 1234
138 Request target
position reached event
send an additional reply when the
motor has reached its target
position
(don't care)
(don't care)
(don't care)
Sge regly farmat 0f command 136:
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 59
www.trinamic.com
Special reply format of command 136:
Type set to 0 - reply as a string:
Byte index
Contents
1
Host Address
29
Version string (8 characters, e.g. 1021V129)
There is no checksum in this reply format!
Type set to 1 - version number in binary format:
Please use the normal reply format.
The version number is output in the value field of the reply in the following way:
Byte index in value field
Contents
1
Version number, low byte
2
Version number, high byte
3
Type number, low byte
(currently not used)
4
Type number, high byte
(currently not used)
BB ht E 255 E 255
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 60
www.trinamic.com
4 Axis Parameters
The following sections describe all axis parameters that can be used with the SAP, GAP, AAP, STAP and
RSAP commands.
Meaning of the letters in column Access:
Access
type
Related
command(s)
Description
R
GAP
Parameter readable
W
SAP, AAP
Parameter writable
E
STAP, RSAP
Parameter automatically restored from EEPROM after reset or power-on. These
parameters can be stored permanently in EEPROM using STAP command and
also explicitly restored (copied back from EEPROM into RAM) using RSAP
Basic parameters should be adjusted to motor / application for proper module operation.
Parameters for the more experienced user please do not change unless you are absolutely
sure.
Number
Axis Parameter
Description
Range [Unit]
Acc.
0
Target (next)
position
The desired position in position mode (see
ramp mode, no. 128).
−2.147.483.648…
+2.147.483.647 [µsteps]
RW
1
Actual position
The current position of the motor. Should only
be overwritten for reference point setting.
−2.147.483.648…
+2.147.483.647 [µsteps]
RW
2
Target (next)
speed
The desired speed in velocity mode (see ramp
mode, no. 128). In position mode, this
parameter is set automatically: to the maximum
speed during acceleration, and to zero during
deceleration and rest.
-268.435.455…
+268.435.454
[pps]
RW
3
Actual speed
The current rotation speed.
-268.435.455…
+268.435.454 [pps]
RW
4
Maximum
positioning
speed
Maximum feasible positioning speed. Has to be
adapted to motor and application
0… +268.435.454
[pps]
RWE
5
Maximum
acceleration
Limit for acceleration and deceleration. Has to
be adapted to motor and application.
1… +33554431
[pps/s]
RWE
6
Max. motor run
current
Attention: setting motor current too high might
permanently damage the motor!
The maximum value is 255. This value means
100% of maximum programmable current of the
selected motor current range (see axis
parameter 179). Current can be adjusted /
scaled down by specifying a lower value
between 0 and 255. This value is transformed
into 32 different internal current settings
supported by the hardware (see hardware
manual for more details).
Please note: high current range is available for
hardware version V1.4, only!
0… 255
Low current range scaling
(axis parameter 179 set to
1):
    

    

High current range scaling
(axis parameter 179 set to
0):
    

   

RWE
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 61
www.trinamic.com
Number
Axis Parameter
Description
Range [Unit]
Acc.
7
Standby current
Current limit after the motor has stopped plus
power down delay time (see parameter 214).
0… 255
(Same range and
current scaling as for
axis parameter 6)
RWE
8
Position reached
1 when target position = actual position
0 otherwise
0/1
R
9
Home switch
status
The logical state of the home switch.
0/1
R
10
Right limit
switch status
The logical state of the (right) limit switch.
0/1
R
11
Left limit switch
status
The logical state of the left limit switch (in
three switch mode)
0/1
R
12
Right limit
switch disable
If set, deactivates the stop function of the right
switch (default: right limit switch disabled)
0/1
RWE
13
Left limit switch
disable
Deactivates the stop function of the left switch
resp. reference switch if set (default: left limit
switch disabled).
0/1
RWE
128
Ramp mode
Automatically set when using ROR, ROL, MST
and MVP.
0: position mode. Steps are generated, when
the parameters actual position and target
position differ. Trapezoidal speed ramps are
provided.
1: velocity mode. The motor will run
continuously and the speed will be changed
with constant (maximum) acceleration, if the
parameter target speed is changed.
0/1
RW
130
Minimum speed
Ramp generation for acceleration and
deceleration begins and ends with this start
and stop value.
0… +268.435.454
[pps]
Default = 0
RWE
140
Microstep
resolution
0
full step
1
half step
2
4 microsteps
3
8 microsteps
4
16 microsteps
5
32 microsteps
6
64 microsteps
7
128 microsteps
8
256 microsteps (default)
0… 8
RWE
161
Double step
enable
Every edge of the cycle releases a
step/microstep. It does not make sense to
activate this parameter for internal use.
Double step enable can be used with step/dir
interface.
0 double step off
1 double step on
0/1
RW
162
Chopper blank
time
Selects the comparator blank time. This time
needs to safely cover the switching event and
the duration of the ringing on the sense
resistor. For low current drivers, a setting of 1
or 2 is good.
0… 3
RW
163
Chopper mode
Selection of the chopper mode:
0 spread cycle
1 classic const. off time
0/1
RW
TMCM-1021 TMCL Firmware V1.29 Manual (Rev. 1.07 / 2014-SEP-30) 62
www.trinamic.com
Number
Axis Parameter
Description
Range [Unit]
Acc.
164
Chopper
hysteresis
decrement
Hysteresis decrement setting. This setting
determines the slope of the hysteresis during
on time and during fast decay time.
0 fast decrement
3 very slow decrement
0… 3
RW
165
Chopper
hysteresis end
Hysteresis end setting. Sets the hysteresis end
value after a number of decrements. Decrement
interval time is controlled by axis parameter
164.
-3… -1
negative hysteresis end setting
0
zero hysteresis end setting
1… 12
positive hysteresis end setting
-3… 12
RW
166
Chopper
hysteresis start
Hysteresis start setting. Please remark, that this
value is an offset to the hysteresis end value.
0… 8
RW
167
Chopper off time
The off time setting controls the minimum
chopper frequency. An off time within the
range of 5µs to 20µs will fit.
Off time setting for constant tOFF chopper:
NCLK= 12 + 32*tOFF (Minimum is 64 clocks)
Setting this parameter to zero completely
disables all driver transistors and the motor can
free-wheel.
0 / 2… 15
RW
168
smartEnergy
current minimum
Sets the lower motor current limit for
coolStep™ operation by scaling the max. motor
run current value (parameter 6).
minimum motor current:
0 1/2 of parameter 6
1 1/4 of parameter 6
0/1
RW